Testing Overview

Our motor testing capabilities include multiple electrical and mechanical tests. Whether upon inspection or client request, motor testing can be completed for a variety of reasons including detecting shorts between lamination, testing for defective rotor bars, testing motor windings and more. Test results will be included in a motor repair report, sent out on applicable motors 100 HP and up, or per Customer requirements.


Electrical Testing

  • Megohmmeter Test - All motor windings will be given a megohmmeter test to ground before disassembly and upon completion of repairs, with results recorded on Bradleys' Insulation Test Data form. The minimum acceptable value of insulation resistance in megohms upon completion of rewinding is 100 megohms.

  • Polarization Index Test - All motor windings rated at 2300 volts and above will be given a one minute versus ten minute polarization index test after completion of repairs, with results recorded on the back of Bradleys' Insulation Test Data form.

  • Surge Comparison Test - Windings will be tested by surge comparison with results recorded on Bradleys' Insulation Test Data form.

  • DC High Potential Test> - Will be performed on all motors according to NEMA MG-1-2 0.47 and Safety and test procedures will be carried out in accordance with NEMA MG-1-3.01.

  • Wet Test - When specified by the Customer, a wet test on the stator will be performed on 2300 and 4160 volt form wound coil motors by water spray method as outlined in NEMA MG-1 - 20.49.2.

  • DC Winding Resistance Test - When specified by the customer or otherwise required, the test will be given all like coils, i.e., individual stator, phase grouped stator - A to B, A to C, and B to C. The DC resistance difference between like coils should not vary more than + or - 0.5%.

  • Core Loop Test - The acceptable method for detecting shorts between lamination will be to induce magnetic flux in the stator core by transformer action. This is accomplished by winding several turns of cable around one side of the stator core, then energizing cable from a low voltage source. Core testing on small motors below approximately 1250 HP will be performed using a 25 KVA core loss tester. Larger motors will be checked using the EASA Stator Core Test Form.

  • Single Phase, Low Voltage Test - When specified by the Customer or otherwise required, a single-phase, low-voltage test (approximately 10% to 20% of rated voltage) will be performed on AC squirrel-cage rotors to find defective rotor bars. Maximum line current variation recommended: < 3% as shaft is rotated with full-load current applied.

  • Mechanical Testing

  • Vibration measurements will be made with the stator winding at full voltage and the motor rotor shaft-coupling hub installed when practical. Vibration levels below .1 inches/second are expected.

  • All sleeve bearing motors will be run at rated voltage for a minimum of 1/2 hour at no load. Bearing temperatures, amperage, and speed are to be measured and recorded on Bradleys' Motor Initial/Final Test form. If motor is to be run at other than rated voltage, the customer will be notified.

  • After motor reaches full speed and rotor stabilizes at magnetic center, a shaft indicator will be installed to indicate center. Maximum travel will be no less than original manufacturer's specifications and magnetic center will be within center band of 1/8 inch.

  • Anti-friction bearing spike energy readings will be taken with a suitable instrument such as an CSI 2130. Readings will be noted on Bradleys' Motor Initial/Final Test form.

  • When required, a lube oil skid and/or oil circulation equipment will be used to simulate actual running conditions. Information such as oil type, oil pressure, temperature, orifice size, and flow (gph) may be required from the customer.

  • Media and Links

    Download PDF Bradleys' Binder

    Details: Complete binder on Bradleys' electric motor repair and maintenance specifications. Learn more about motor voltage and testing voltage for Bradleys' electrical tests as well as examples of data sheets used.